Heat meters via M-Bus (POL937)
The POL937 module reads M-Bus meters and provides the values to the S400 via the internal extension bus. What matters in practice:
- Know the addresses in advance: there is no automatic meter scan - primary and secondary addresses must be known.
- Adjust the polling interval: the factory setting reads hourly. For control purposes the interval must be reduced to a few seconds.
- Mind the meter dynamics: depending on the meter type, the meter itself only updates every few seconds - fast control loops need fast sensors.
- Read the LED correctly: a red bus LED is normal without a running application; orange indicates incorrect parameterisation.